up to 132 HP
Technical Data
KG125
Standard Motor Load (DOL-Rating):
3 x 120V [HP]: 15
3 x 240V [HP]: 30
3 x 480V [HP]: 60
Ampere Rating:
3 x 277V [A]: -
3 x 600V [A]: 125
Thermal Current: lu/lth [A]: 125
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 45 / AC-3 [kW]: 37
KG160
Standard Motor Load (DOL-Rating):
3 x 120V [HP]: 20
3 x 240V [HP]: 40
3 x 480V [HP]: 60
Ampere Rating:
3 x 277V [A]: -
3 x 600V [A]: 160
Thermal Current: lu/lth [A]: 160
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 55 / AC-3 [kW]: 45
KG210
Standard Motor Load (DOL-Rating):
3 x 120V [HP]: 25
3 x 240V [HP]: 50
3 x 480V [HP]: 75
Ampere Rating:
3 x 277V [A]: -
3 x 600V [A]: 200
Thermal Current: lu/lth [A]: 200
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 75 / AC-3 [kW]: 55
KG250
Standard Motor Load (DOL-Rating):
3 x 120V [HP]: 30
3 x 240V [HP]: 60
3 x 480V [HP]: 75
Ampere Rating:
3 x 277V [A]: -
3 x 600V [A]: 250
Thermal Current: lu/lth [A]: 250
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 90 / AC-3 [kW]: 55
KG315
Standard Motor Load (DOL-Rating):
3 x 120V [HP]: 40
3 x 240V [HP]: 75
3 x 480V [HP]: 100
Ampere Rating:
3 x 277V [A]: -
3 x 600V [A]: 315
Thermal Current: lu/lth [A]: 315
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 110 / AC-3 [kW]: 75
C316
Standard Motor Load (DOL-Rating):
3 x 120V [HP]: 30
3 x 240V [HP]: 75
3 x 480V [HP]: 75
Ampere Rating:
3 x 277V [A]: -
3 x 600V [A]: 240
Thermal Current: lu/lth [A]: 315
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 132 / AC-3 [kW]: 55
Switching Function:
- ON/OFF-Switches
2, 3, 4, 6 and 8 pole